LD | MD | - | □ | / | □ | R | □ |
↓ | ↓ | ↓ | ↓ | ↓ | ↓ | ||
Model Description | Surge protector Device (SPD) | Maximum discharge current | 1P、2P、3P、4P | With remote signaling or communication and remote alarm | Lightning protection level (T1) |
Model | LD-MD-A12.5 | LD-MD-A15 | LD-MD-A25 | LD-MD-A50 | |
SPD Ports | 1 | 1 | 1 | 1 | |
SPD Category | Voltage limiting type/Voltage switching type | Voltage limiting type/Voltage switching type | Voltage switching type | Voltage switching type | |
Test Category | I | I | I | I | |
Rated Voltage Un | 220V AC50~60Hz | 220V AC50~60Hz | 220V AC50~60Hz | 220V AC50~60Hz | |
Maximum continuous operating voltage (AC) Uc | 275V、320V、385V、420V、440V | 275V、320V、385V、420V、440V | 275V、320V、385V、420V、440V | 275V、320V、385V、420V、440V | |
Insulation resistance | >100MΩ | >100MΩ | >100MΩ | >100MΩ | |
Impulse discharge current(10/350μs)limp | 12.5kA | 15kA | 25kA | 50kA | |
Voltage protection level(1.2/50μs)Up | 2.2kV | 2.2kV | 2.5kV | 2.8kV | |
Response time tA | ≤100ns | ≤100ns | ≤100ns | ≤100ns | |
Size mm | P36mm/ large volume | 144×90×66 | 144×90×66 | 144×90×66 | 144×90×66 |
P18mm/ small volume | 72×90×66 | 72×90×66 | 72×90×66 | / | |
Installation wire cross-sectional area mm2 | 6~25 | 6~25 | 6~25 | 6~25 | |
Installation method | Standard rails 35mm(EN50022/DIN46277-3) | ||||
Operating temperature | -40~85℃ | ||||
Shell material | PA66(small volume)、Plastic(large volume),Comply with UL94 V-0 | ||||
Class of protection | IP20 |